Sensor Types
                                
                                
                                    4-20 mA with or without HART, Supports 2-wire and 4-wire device types
                                
                             
                            
                                
                                    Nominal signal range (span)
                                
                                
                                    4-20 mA, (0-20 mA optional)
                                
                             
                            
                                
                                    Full signal range
                                
                                
                                    0 to 22 mA
                                
                             
                            
                            
                                
                                    Field Power (2-wire)
                                
                                
                                    16.0 V(min) at 20 mA
                                
                             
                            
                                
                                    Accuracy over temperature range
                                
                                
                                    0.1% of span (0-60° C), 0.25% of span (over -40 -70°C)
                                
                             
                            
                                
                                    Repeatability
                                
                                
                                    0.05% of span
                                
                             
                            
                                
                                    Resolution
                                
                                
                                    16 bit A/D converter
                                
                             
                            
                                
                                    Isolation
                                
                                
                                    Galvanically isolated according to EN 60079-11. Voltage peak value 375 VDC.
                                
                             
                            
                                
                                    CHARM Power Req.
                                
                                
                                    60 mA max @ 24 VDC ±10%
                                
                             
                            
                                
                                    CHARM Heat Dissipation
                                
                                
                                    0.86 W
                                
                             
                            
                                
                                    HART Support
                                
                                
                                    HART v7 pass-through for AMS, HART v7 variable and device status available to control
                                
                             
                            
                                
                                    HART Data Update Rates
                                
                                
                                    Update rates are faster than every second dependent on HART communication loading and device type